Get a Quote
Sensor-controlled lighting is the rare energy upgrade with a payback under two years — when the sensor technology matches the building. Spec the wrong detection principle for a high-rack warehouse and you get flickering aisles, complaints, and a retrofit that gets switched off in month three. Here is how the technologies differ and how to build an ROI number a CFO signs off.
| Technology | How it detects | Strengths | Limits | Best fit |
|---|---|---|---|---|
| PIR (passive infrared) | Warm-body heat movement across zones | Cheap, reliable, low false triggers | Needs line of sight; range drops at height; blinds behind racking | Offices, corridors, low halls (≤ 4–5 m) |
| Microwave (Doppler) | Radio echo shift from any motion | Sees through plastic, glass and thin partitions; works at 8–14 m mounting | Detects motion outside the room if sensitivity unadjusted; slightly higher cost | Warehouses, high-bay, cold rooms |
| Daylight harvesting | Photocell dims against window light | Captures free daylight automatically | Needs commissioning per zone | Perimeter aisles, skylit halls |
| High-frequency hybrid | Microwave + daylight cell in one unit | One device, full control | Commissioning still required | New warehouse fit-outs |
The height rule is the one buyers forget: a PIR sensor mounted at 10 m over a warehouse aisle watches a tiny floor footprint and cools down slowly. Microwave at the same height covers long aisles and reacts to a forklift a full bay away.
Savings come from what happens when nobody is there. The two strategies:
Real occupancy data from logistics facilities puts aisles at 30–50% occupied during operating hours, and near zero overnight. That vacant share is the entire business case.
Worked example — a 100-fixture warehouse, UFO high bays at 150 W, 12 operating hours/day, electricity at €0.15/kWh, microwave dim-to-low controls:
| Line | Baseline (no sensors) | With dim-to-low sensors |
|---|---|---|
| Installed load | 100 × 150 W = 15 kW | 100 × 150 W + 1 W sensor ≈ 15.1 kW |
| Annual burn @ 12 h/day | 15 kW × 4,380 h = 65,700 kWh | Occupied 40% at full + 60% at 15% ≈ 31,800 kWh |
| Annual energy cost | €9,855 | €4,770 |
| Annual saving | — | ≈ €5,085 |
| Sensor control adder (typical) | — | €12–18 per fixture installed |
| Simple payback | — | Under 5 months |
Even at half the occupancy savings — say the facility runs three shifts — payback stays inside twelve months. The sensitivity: electricity tariff and actual occupancy. Ask your supplier for a DIALux + occupancy simulation against your shift pattern rather than a brochure percentage.
No — unlike HID, LEDs do not suffer from switching cycles. A quality driver rated for frequent on/off exceeds the fixture's own service life. Dimming to 10–20% can actually extend driver electrolytic-capacitor life by reducing heat.
Yes — master-slave wiring lets one sensor unit switch or dim a linked run, cutting sensor cost per meter. For warehouses we usually recommend per-fixture microwave sensors on high bays and master-slave on linear batten rows.
Settings solve this: hold-off time (how long after last detection), and for offices a presence-sensitivity mode that detects small movements like typing. Commissioning is where good projects separate from nuisance-flicker projects.
Scale it: halve the tariff and the example above still pays back in about ten months. The other driver is regulation — the EU EPBD and local codes increasingly mandate controls in new and renovated commercial buildings, so the baseline comparison itself is disappearing.
Send operating hours, tariff and aisle layout — we return a DIALux-based sensor strategy with real kWh numbers.